电梯前室压力传感器
正压送风压力传感器工作原理:正常情况下正压送风机通过风管往风井中加压送风(绿色箭头方向),加压后的风再分别通过每层的百叶窗或风阀送往每层的前室或楼梯间。当消防前室或楼梯间的通风压力或压差超过设定值(前室25~30pa,楼梯间40-50pa)时,位于每层的压力传感器顺即时发出信号报警输入旁通泄压阀控制箱,旁通泄压阀控制箱根据压力传感器的信号打开旁通泄压阀,旁通泄压阀打开后,部分加压送风机送往风管的风通过旁路风管经过旁通泄压阀回到风机前端(红色箭头位置),从而减少送往前室及楼梯间的风压,降低前室及楼梯间的风压值。当前室或楼梯的风压值降低到设定值时,旁通泄压阀自动关闭,从而实现前室及楼梯间压力自动控制,---疏散通道烟雾不会倒灌进入前室及楼梯间,---人群疏散的安全。

当消防前室或楼梯间的通风压力或压差超过设定值(前室25~30pa,楼梯间40-50pa)时,working principle of itive pressure air supply pressure sensor: under normal circumstances, the itive pressure air supply fan pressurizes the air supply into the air shaft through the air duct (green arrow direction) , the compressed air is then sent to the front room/stairwell of each floor through the shutters/the air valve. when the ventilation pressure/pressure difference in the fire chamber/stairwell exceeds the set value (25 ~ 30 pa in the front chamber&40-50 pa in the stairwell) , the pressure sensor located on each floor immediately sends a signal to the by-pass pressure relief valve control box, the by-pass pressure relief valve control box opens the by-pass pressure relief valve according to the pressure

前室压力传感器
---相当于传感与控制器一个新方向的采合.性价同等产品---.
4:表面有精细巡检指示灯与报.当工作时巡检指示灯绿灯亮起,当感应到风压过---红灯亮起并有无源开关动作.
主要应用在消防正压送风感测压差高要求控制泄压阀,余压阀动作.---要求压差控制为目的工业系统中运用. 此产品也称之为正压送风传感器,压差测控器,风压差传感器等!
测量范围: 0~100pa
耐 压:1000pa
product features are: 1: the use of sensing technology, core components imported core body. 2:&directly change the sensor signal into changeable passive switch signal with microprocessor circuit.