德州紫旭空调设备有限公司提供消防楼梯间前室压力传感器-豪鲁邦空调。
前室压力传感器消防楼梯间前室压力传感器hlb-20电梯前室压力传感器采用标86盒嵌入式准安装,采用汉字液晶实时显示被管理的压力传感器工作状态,消防楼梯间前室压力传感器安装位置,可显示超压故障报警信息;系统总线采用nh-rvs-4×1.5 mm2通信及供电,沿楼梯间、前室楼板垂直敷设,500米并联连接链接52台压力传感器;
4、hlb-20电梯前室压力传感器通过通信接口并联接入加压风机控制箱内消防电源监控系统总线,将系统工作状态实时上传至消---制室内的压力传感器进行存储,以便于值班人员随时掌握和了解设备运行情况;





电梯前室压力传感器

当消防前室或楼梯间的通风压力或压差超过设定值(前室25~30pa,消防楼梯间前室压力传感器接线,楼梯间40-50pa)时,working principle of itive pressure air supply pressure sensor: under normal circumstances, the itive pressure air supply fan pressurizes the air supply into the air shaft through the air duct (green arrow direction) , the compressed air is then sent to the front room/stairwell of each floor through the shutters/the air valve. when the ventilation pressure/pressure difference in the fire chamber/stairwell exceeds the set value (25 ~ 30 pa in the front chamber&40-50 pa in the stairwell) , the pressure sensor located on each floor immediately sends a signal to the by-pass pressure relief valve control box,消防楼梯间前室压力传感器厂家, the by-pass pressure relief valve control box opens the by-pass pressure relief valve according to the pressure


于压差传感器,消防楼梯间前室压力传感器,在我们甲方群里有几点疑问:
1、 这个压差传感是给消防做还是弱电做?
2、 压差传感如何安装?
就这两个问题,以下做一个系统的总结和交流。
一、划在哪个标段?
压力传感器控制系统其实是一套独立的联动系统,可以是弱电做也可以是消防来做,但是后都要消防来调试并负责验收,所以个人建议为避免扯皮,还是放在消防标段比较合适。
二、如何安装?
要谈如何安装,先介绍一下系统:
这个系统主要为控制柜、线路和末端传感器三个部分。



消防楼梯间前室压力传感器-豪鲁邦空调由武城县豪鲁邦空调设备有限公司提供。行路致远,---。武城县豪鲁邦空调设备有限公司致力成为与您共赢、共生、共同前行的---,更矢志成为继电器具有竞争力的企业,与您一起飞跃,共同成功!
联系我们时请一定说明是在100招商网上看到的此信息,谢谢!
本文链接:https://tztz322798.zhaoshang100.com/zhaoshang/266892097.html
关键词: